welcome to Haiyuan water treatment Co. Ltd English|Spainsh|Online message
> Reverse Osmosis plant/system

The current position:Home > Blog > Reverse Osmosis plant/system

Maintenance troubleshooting Reverse osmosis pure water equipment

            HYWATER        Reverse Osmosis plant/system

Maintenance troubleshooting Reverse osmosis pure water equipment


1) The switch is turned on, but the euiqment does not start.

- Electrical circuit failure, such as broken fuse, wire falling off

- The thermal protection element is not reset after protection

- The waterway is under-voltage, check the insurance, check the wiring

- The thermal protection element is reset

- Check the waterway to ensure the water supply pressure

 

2) After the equipment is started, the inlet water solenoid valve does not open.

- The wiring is disconnected

- Internal mechanical failure of solenoid valve

- Solenoid valve coil is broken

- Check the line

- Remove the solenoid valve for maintenance

- Repair or replace the coil

 

3) Pump runs but not at rated pressure and flow.

- Pump reverse

- Cartridge filter be blocked

- There is air in the pump

- Flush solenoid valve open

- Rewiring

- Clean or replace the filter element

- Remove the air in the pump

- Adjust the pressure after flushing

 

4) The solenoid valve does not close after flushing.

- Solenoid valve control element and circuit failure

- Solenoid valve mechanical failure

- Check or replace components and lines

- Remove the solenoid valve, repair or replace it

 

5) The concentrated water pressure cannot reach the rated value.

- Pipeline leakage

- The flushing solenoid valve is not fully closed

- Leakage of recovery system

- Check and repair the pipeline

- Check and replace the flushing solenoid valve

- Check and repair the recycling system

 

6) Product water quality deteriorates.

- Membrane be blocked and scaled

- Membrane junction seal aging failure

- Chemical cleaning according to technical requirements

- Replace the O-ring

- Replace the membrane

 

More inquiries related to Reverse osmosis pure water equipment please contact:

Mob& Wechat& WhatsApp: (+86)13544774483

Email: sales010@water-sy.com

 

We will provide high-quality, all-round comprehensive professional services for project consulting, system design, manufacturing, installation and commissioning, personnel training, etc

Prev: Reverse osmosis filtration system pharmaceutical waste water deep treatment (2)

Next:Sistema de filtración de ósmosis inversa tratamiento profundo de aguas residuales farmacéuticas (2)

©2121 HY water, Ltd All Rights reserved.
Industrial & drinking Reverse osmosis water purification system,Seawater desalinaton plant in Africa, Asia, Europe, South America, Australia |Made in China by Haiyuan. an ISO9001:2019 Certified Company Add: Xiansha Gaobu Town,Dongguan city,Guangdong,China|+86(769)88706055| Email:sales@seawaterroplants.com